IRTUM – Institutional Repository of the Technical University of Moldova

Implementarea tehnologiilor inovaţionale în reţele electrice de distribuţie (6-35 kV)

Show simple item record

dc.contributor.advisor STRATAN, Ion
dc.contributor.author MERENEANU, Gheorghe
dc.date.accessioned 2021-02-11T10:49:23Z
dc.date.available 2021-02-11T10:49:23Z
dc.date.issued 2019
dc.identifier.citation MERENEANU, Gheorghe. Implementarea tehnologiilor inovaţionale în reţele electrice de distribuţie (6-35 kV): tz. de master: Programul de studiu: Electroenergetica. Cond. şt. STRATAN Ion. Universitatea Tehnică a Moldovei. Chişinău, 2019. en_US
dc.identifier.uri http://repository.utm.md/handle/5014/12855
dc.description Fișierul atașat conține: Rezumat, Abstract, Cuprins, Introducere. en_US
dc.description.abstract În cadrul lucrării a fost studiat implimentarea tehnologiilor inovaționale în rețelele electrice de distriuție (6-35) kV și anume utilizarea recloser-lui în rețelele electrice de distribuție, influența utilizării transformatoarelor cu diferite scheme de conexiune a înfășurărilor și a diferitor tipuri de conductoare asupra parametrilor rețelei electrice. Detaliat în capitolul doi s-a descris construcția recloser-lui și principiul de funcționare. Tot în capitolul doi a fost studiat care este avantajul recloser-lui poziționat în diferite locuri ale rețelei electrice. În capitolul trei ca studiu de caz a fost determinat locul optim de amplasare a recloser-lui cât și durata totală de restabilire a alimentării cu energie electrică a consumatorilor. Efectuând calculele și analizând influența recloser-lui asupra parametrilor ce influențează stabilitatea alimentării cu energie electrică a consumatorilor s-a observat că cantitatea de energie nelivrată consumatorilor într-o rețea cu alimentare bilaterală se micșorează de 6,06 ori iar în cazul unei RED cu alimentare unilaterală și cu secționare automată de 3,3. Efectuând calculul economic s-a demonstrat că pentru recuperarea investițiilor este necesar de 6,1 ani. În capitolul patru sa studiat schemele de conexiiune a transformatorelor de medie tensiune de puteri mici și medii și influența acestora asupra calității energiei electrice. După efectuarea calculelor s-a determinat că utilizarea transformatoarelor cu conexiunea Y / Z  0 ne permite sa reducem coeficientul privind pierderile de putere activă cauzate de curenții nesimetrici, de 9 ori față de transformatorul cu schema de conexiune Y / Y 0 și de 5 ori față de transformatorul cu schema de conexiune Y / Y 0 cu dispozitiv de simetrizare. Tot în capitolul patru a fost analizată influența conductoarelor izolate torsadate de medie tensiune de tip SIP-3 asupra parametrilor energiei electrice. Din analizele prezentate în lucrare rezultă că în reţelele de 10 kV cu conductoare izolate torsadate, au loc reducerea pierderilor de tensiune cu circa 5,4%; pierderilor de putere reactivă 9.3% şi, respectiv, pierderilor de putere activă cu 0,1%, față de rețelele cu conductoare neizolate. en_US
dc.description.abstract In this paper was studied the implementation of the innovative technologies in the electrical distribution networks (6-35) kV and especially use of recloser in electrical distribution grids, the influence of the use of transformers with different schemes of connection of the windings and of different types of conductors on the parameters of electrical network. In chapter two was described in detail construction and operating principle of recloser. Also in chapter two was analyzed the advantage of recloser which is installed in different places of electrical network. Chapter three contains as case study the determination of the optimal place for installing recloser also the total duration of restoration of electrical suplly for the consumers. Performing all these calculations and analyzing the influence of the recloser on the parameters that influence on the reliability of the electricity supply of the consumers it was observed that the amount of energy delivered to the consumers in a network with a bilateral power supply is reduced by 6.06 times and in the case of a RED with unilateral supply and with automatic sectioning 3.3. The realization of economic calculation also showed that 6.1 years are required for the recovery of investments. In the fourth chapter was studied the connection schemes of medium voltage low power transformers and their influence on the quality of electrical energy. After performing the calculations it was determined that the use of transformers with the connection Y / Z  0 allows us to reduce the coefficient, which is related to the losses of active power caused by the asymmetric currents, 9 times compared to the transformer with the connection scheme Y / Y 0 and 5 times compared to the transformer with the connection scheme with Y / Y 0 SD. Also in chapter four was analyzed the influence of medium voltage insulated conductors of type SIP-3 on the parameters of electricity. Performing the analysis results that in electrical distribution networks 10 kV with twisted insulated conductors, the voltage losses decrease by about 5.4%; reactive power losses by 9.3% and active power losses respectively by 0.1%. en_US
dc.language.iso ro en_US
dc.publisher Universitatea Tehnică a Moldovei en_US
dc.rights Attribution-NonCommercial-NoDerivs 3.0 United States *
dc.rights.uri http://creativecommons.org/licenses/by-nc-nd/3.0/us/ *
dc.subject implimentare a tehnologiilor inovaționale en_US
dc.subject rețele electrice de distriuție en_US
dc.subject recloser en_US
dc.title Implementarea tehnologiilor inovaţionale în reţele electrice de distribuţie (6-35 kV) en_US
dc.type Thesis en_US


Files in this item

The following license files are associated with this item:

This item appears in the following Collection(s)

Show simple item record

Attribution-NonCommercial-NoDerivs 3.0 United States Except where otherwise noted, this item's license is described as Attribution-NonCommercial-NoDerivs 3.0 United States

Search DSpace


Browse

My Account